Voltage Drop Calculator

Estimate wire voltage drop, percentage and voltage at the load from current, length, AWG and material.

Your files stay on this device

Files are processed in your browser, never uploaded. The site downloads code and assets to run the tools. No accounts or trackers.

Use Download to save this tool as one HTML file for offline use.

Privacy →

About this tool

Voltage Drop Calculator is a free, in-browser tool that estimates how much voltage a wire run loses under load. It runs entirely in your browser and uploads nothing.

The conductor cross-section comes from the AWG number using A = π/4·(0.127 mm × 92^((36 − n)/39))². The drop is Vdrop = factor · L · I · ρ / (A·10⁻⁶), where L is the one-way length in metres, I the current, ρ the resistivity (copper 1.724×10⁻⁸, aluminum 2.82×10⁻⁸ Ω·m), and the factor accounts for the circuit: 2 for DC or single-phase (there and back) and √3 ≈ 1.732 for three-phase. The percentage drop is Vdrop / Vsource × 100 and the voltage at the load is Vsource − Vdrop. A flag warns when the drop exceeds 3%, the level NEC recommends staying under for branch circuits.

Use it to check whether a cable run is thick enough: if the percentage is over 3%, step up to a larger wire (a lower AWG number), shorten the run, or raise the supply voltage.

Frequently asked questions

What is the voltage drop formula?
Vdrop = factor · L · I · ρ / A, where L is the one-way length in metres, I the current, ρ the conductor resistivity and A the cross-section in m². The factor is 2 for DC and single-phase circuits and √3 for three-phase.
Why is the factor 2 for DC and single-phase?
Current flows out along one conductor and back along another, so the resistive path is twice the one-way length — hence a factor of 2. Three-phase uses √3 because of the phase relationship between conductors, not a simple round trip.
What does the 3% flag mean?
The US National Electrical Code recommends keeping branch-circuit voltage drop under 3% (and about 5% total including the feeder). The tool flags any result above 3% so you know to use a heavier conductor or a shorter run.
Is my data uploaded?
No. The current, length, gauge and voltage are processed entirely in your browser; nothing is sent to a server and the calculator works offline.